Line hose
|
Blankets and Accessories |
Switchboard Matting
Linemen's Gloves |
Leather Glove Protectors |
Glove Kits, Accessories, and Storage
Glove Kits, Accessories, and Storage
|
Glove Kits and
Storage Bags
|
|
|
|
|
|
|
Proper storage extends the service life of
linemen’s gloves and sleeves.
Folds and creases strain rubber and cause it to
crack from ozone prematurely. By storing rubber
gloves in the right size bag, and never forcing
more than one pair into each bag, equipment will
lie flat and last longer.
Salisbury bags are constructed of heavy duty
canvas duck and are double stitched and riveted
at stress points for extra durability. Canvas bags
feature a D ring for hanging in trucks or on work
belts. Bags feature tapered gussets with wide
opening tops for easy insertion.
New Glove and Protector
Bags contain two layered
pockets in one bag.
Now, both a pair of
gloves and protectors
can be properly
stored in one
convenient bag.
SALISBURY ADVANTAGE
Glove Kits
Salisbury’s insulating rubber gloves are necessary
for every electrical worker’s complete safety. And
to insure your safety, Salisbury’s leather
protectors provide needed protection from cuts,
abrasions, and punctures. To keep these safety
items in top condition, proper storage is very
important
. |

|
Cat No. |
For Glove Length in. (mm) |
Dimensions in. (mm) |
Weight ea. lbs. (kgs) |
|
26 oz. Canvas Glove Bags |
|
GB112 |
11 (280) |
9" x 14" (229 x
356) |
1 (.5) |
|
GB114 |
14 (356) |
9" x 16" (229 x
406) |
1 (.5) |
|
GB116 |
16 (406) |
9" x 18" (229 x
457) |
1.2 (.6) |
|
GB118 |
18 (457) |
9" x 20" (229 x
508) |
1.5 (.7) |
|
26 oz. Canvas Glove
Bags w/ goggle case |
|
GB114GC |
14 (356) |
9" x 16" (229 x
406) |
1 (.5) |
|
GB116GC |
16 (406) |
9" x 18" (229 x
457) |
1.2 (.6) |
|
GB118GC |
18 (457) |
9" x 20" (229 x
508) |
1.5 (.7) |
|
14.75 oz. Canvas
Glove & Protector Bags |
|
GPB114 |
14 (356) |
9" x 16" (229 x
406) |
1 (.5) |
|
GPB116 |
16 (406) |
9" x 18" (229 x
457) |
1.2 (.6) |
|
GPB118 |
18 (457) |
9" x 20" (229 x
508) |
1.5 (.7) |


Click for ASTM Labeling Chart
|
|
Product Numbering Chart for Glove Kits |
|
ASTM Class |
Length (inches) |
Color |
Size |
| |
|
|
|
|
GK00 |
11" or 14" |
B, R, Y, BL |
7, 8, 9, 10,
11, 12 |
|
GK0 |
11" or 14" |
B, R, Y, BL |
7, 8, 9, 10,
11, 12 |
|
GK2 |
14", 16", or
18" |
B, RB, YB |
7, 8, 9, 10,
11, 12 |
| |
|
|
|
|
Example:
GK011BL/9 |
|
Type I Natural
Rubber available in: Red (R), Yellow
(Y), Black (B), Red / Black (RB) |
|
Type II SALCOR
Rubber available in: Blue (BL) |
|
| |
|
|
Inspection
Equipment |
|
| |
|
|
OSHA 1910.137 states
“Insulating equipment shall be inspected
before each day’s use and immediately
following
any incident that can reasonably be
suspected of having
caused damage. Insulating gloves shall be
given an air test,
along with the inspection.” Salisbury’s
New G100 (Patent
Pending), with G100A adapter for Class 00
and 0 and smaller
size gloves, and the G99, without
additional adapter, are the
perfect answer for inflating your gloves
for inspection.
The G99 is a simple, easy to use, portable
glove inflator.
The G99 provides a quality means of
inspecting gloves in
the field. The glove is secured to the
inflator using a nylon
strap and fastened with a hook and pile
closure. Inflation
is accomplished by pumping the bellows of
the inflator
against any surface. NOTE: gloves should
be expanded
no more than 1.5 times their normal size
for Type I,
and 1.25 times normal for Type II SALCOR.
SALISBURY ADVANTAGE
The G100 is also a simple and easy to use,
portable glove
inflator. The G100 operates exactly like
the G99, but includes
an additional G100A adapter to also
inspect Class
00 and 0 and smaller gloves. To use the
adapter, the glove
is secured to the G100A adapter using a
nylon strap with a
hook and pile closure. The adapter, with
glove attached, is
then placed on top of the inflator to be
inflated for inspection.
In the test lab or service center, the
G1
and
G2 glove inflators are preferred. Both can
be pneumatically operated, large
quantities
of gloves can be inspected in minimal
time.
The G1 is pedestal mounted and does not
require
connection to a source of compressed
air. The G1 provides maximum efficiency forp
testing large quantities of gloves.
The G2 bench mounted inflator is ideal for
smaller quantities of gloves. This
inflator can
either be pneumatically operated or by a
built
in hand pump. |

| |
Cat no. |
Description |
Weight Ea. lbs. (mm) |
| |
|
|
|
| |
G99 |
Glove Inflator
Kit |
2 (.91) |
| |
G99B |
Replacement Bag |
- |
| |
G99S |
Replacement Strap |
- |
| |
G99V |
Replacement Check
Valve |
- |
| |
G1 |
Pedestal w/ Foot
Control |
45 (20.4) |
| |
G2 |
Bench Type w/
Hand Pump |
40 (18.1) |
| |
G100 |
Glove Inflator
Kit w/ Adapter |
- |
| |
G100A |
Low-Volt Glove
Adapter |
- |
|
|
|
|
|
|
|
|
|
|
Page | 1 | 2
| 3
| 4
| 5
| 6
|
|